Composition
100% Polyester non-woven fabric
Semi-conductive bonder
Application
Separating, binding /Between Power cable components
Property | Unit | YCD-14 | YCD-16 | YCD-20 | YCD-22 | YCD-25 | YCD-30 | Test method |
---|---|---|---|---|---|---|---|---|
Thickness | mm | 0.14±0.03 | 0.16±0.03 | 0.20±0.03 | 0.22±0.03 | 0.25±0.03 | 0.30±0.03 | ISO9073-2 |
Mass per unit area | g/m² | 40±10 | 50±10 | 60±10 | 70±10 | 90±10 | 110±10 | ISO9073-1 |
Tensile strength | N/cm | ≥26 | ≥33 | ≥40 | ≥50 | ≥60 | ≥70 | ISO9073-3 |
Elongation | % | ≥12 | ≥12 | ≥12 | ≥12 | ≥12 | ≥12 | ISO9073-3 |
Short term stability | ℃ | 230 | 230 | 230 | 230 | 230 | 230 | YS Method |
Long term stability | ℃ | 90 | 90 | 90 | 90 | 90 | 90 | IEC 216 |
Surface Resistance | Ω | ≤1500 | ≤1500 | ≤1500 | ≤1500 | ≤1500 | ≤1500 | DIN53482 |
Volume Resistance | Ω·m | <1×10⁶ | <1×10⁶ | <1×10⁶ | <1×10⁶ | <1×10⁶ | <1×10⁶ | DIN54345 |
Moisture content | % | ≤9 | ≤9 | ≤9 | ≤9 | ≤9 | ≤9 | ISO287 |